RPS-UPS-Razor RPS-UPS-Razor
Part Number: RPS-UPS-Razor
Razor Series 1000VA - 10kVA Parallel Redundant Tower/Rack Convertible UPS

The Razor Uninterrupted Power Supply is a rack/tower convertible UPS with a double conversion topology that provides pure sinewave output and surge protection for industrial, IT, data center, communication, and other mission-critical equipment. The Razor UPS boasts one of the highest output factors of 1.0 and the lowest Total Harmonics Distortion (THD), making it ideal for sensitive devices. The system also comes with hot-swappable batteries to produce a constant power supply and eliminate costly downtimes. Additionally, the Diagram LCD panel displays immediate and accurate data on the UPS battery and power conditions, which helps users detect potential problems. To extend total runtime, an external battery pack can be provided.

Main benefits:
  • Huge cost savings due to high efficiency and 1.0 power factor output.
  • Guaranteed zero downtime with hot-swappable batteries for constant operation and easy maintenance.
  • Ideal for sensitive equipment and devices due to low Total Harmonics Distortion (THD).
  • Early problem detection with user-friendly and multi-function Diagram LCD.
  • Maximum protection of valuable equipment with overload, surge, and short circuit protection.
UPS
ModelPSR 1000PSR 1500PSR 2000PSR 3000PSR 2000 (2U+2U)PSR 3000 (2U+2U)PSR 6000PSR 10000
Capacity (VA)100015002000300020003000600010K
Capacity (Watts)9001350180027001800270054009K
FormTower or Rack
PhaseSingle Phase
Energy SavingYes - ECO mode Efficiency > 94%
INPUT
Voltage100 / 110 / 115 / 120 / 127 / 208 / 220 / 230 / 240 Vac208 / 220 / 230 / 240 Vac
Voltage Range110 Vac60 ~ 144 Vac < 25% Load
70 ~ 144 Vac < 50% Load
80 ~ 144 Vac < 75% Load
90 ~ 144 Vac < 100% Load
120 ~ 276 Vac < 25% Load
140 ~ 276 Vac < 50% Load
160 ~ 276 Vac < 75% Load
180 ~ 276 Vac < 100% Load
220 Vac120 ~ 276 Vac < 25% Load
140 ~ 276 Vac < 50% Load
160 ~ 276 Vac < 75% Load
180 ~ 276 Vac < 100% Load
Frequency Range50 / 60 Hz (Auto Sensing)
Power Factor> 0.97
Cold StartYes
OUTPUT
Rated Power Factor0.9
WaveformPure Sine Wave
Voltage100 / 110 / 115 / 120 / 127 / 208 / 220 / 230 / 240 Vac ± 2%208 / 220 / 230 / 240 Vac ± 2%
Frequency50 / 60 Hz ± 0.25 Hz
Transfer Time0 ms
Harmonic Distortion≤ 2.5% THD at Linear Load≤ 3% THD at Linear Load
Crest Factor3 : 1
EPO FunctionOption
PROTECTION
OverloadLine Mode105% - 120% for 30 seconds
121% - 150% for 10 seconds
Battery Mode101% - 109% for 10 seconds
110% - 120% for 3 seconds
Surge ProtectionIEC 61000-4-5 Level 3
BypassInternal Bypass (Automatic and Manual)
Short Circuit ProtectionUPS Output Cut Off Immediately
BATTERY
ModelPSB-1000PSB-1500PSB 2000PSB 3000PSB 2000 (2U+2U)PSB 3000 (2U+2U)PSB-6000PSB-10000
Type12V 7Ah12V 7Ah12V 7Ah12V 9Ah12V 7Ah12V 7Ah12V 7Ah12V 9Ah
Quantity3466682020
Sealed, Maintenance FreeYES
Typical Recharge Time4 Hr to 90%
External Battery ModuleOption
External Battery ConnectorOption
MANAGEMENT
IndicatorLCD Control Panel
Communication PortRS232, USB (B-type)
SNMP SlotOption
Audible AlarmsYES
PHYSICAL
Power ModuleDimensions (WxDxH) (In)16.9 x 16.8 x 3.316.9 x 19.9 x 3.316.9 x 25 x 3.316.9 x 16.8 x 3.316.9 x 23.5 x 5.2 (3U)16.9 x 25.9 x 5.2
Weights (Lbs)3639.565.77222.344.155.1
Shipping Dimensions (WxDxH) (In)21.5 x 21.7 x 8.121.7 x 24.5 x 8.721.7 x 29.5 x 8.721.5 x 21.7 x 8.122.1 x 29.2 x 10.822.3 x 31.7 x 8.2
Weights (Kgs)42.846.37580.729.15369

* While 208V output, capacity will derated to 90%
* Specifications are subject to change without further notice
* Specifications are for reference, actual information should be based on real product

UPS
ModelPST-1000PST-1500PST-2000PST-3000PST-6000PST-10000
Capacity (VA)1000150020003000600010000
Capacity (Watts)90013501800270054009000
FormTower
PhaseSingle Phase
Energy SavingYes - ECO mode Efficiency > 94%
INPUT
Voltage100 / 110 / 115 / 120 / 127 or 208 / 220 / 230 / 240 Vac208 / 220 / 230 / 240 Vac
Voltage Range110 Vac60 ~ 144 Vac < 25% Load
70 ~ 144 Vac < 50% Load
80 ~ 144 Vac < 75% Load
90 ~ 144 Vac < 100% Load
120 ~ 276 Vac < 25% Load
140 ~ 276 Vac < 50% Load
160 ~ 276 Vac < 75% Load
180 ~ 276 Vac < 100% Load
220 Vac120 ~ 276 Vac < 25% Load
140 ~ 276 Vac < 50% Load
160 ~ 276 Vac < 75% Load
180 ~ 276 Vac < 100% Load
Frequency Range50 / 60 Hz (Auto Sensing)
Power Factor> 0.97
Cold StartYes
OUTPUT
Rated Power Factor0.9
WaveformPure Sine Wave
Voltage100 / 110 / 115 / 120 / 127 or 208 / 220 / 230 / 240 Vac ± 2%208 / 220 / 230 / 240 Vac ± 2%
Frequency50 / 60 Hz ± 0.25 Hz
Transfer Time0 ms
Harmonic Distortion≤ 2.5% THD at Linear Load≤ 3% THD at Linear Load
Crest Factor3 : 1
EPO FunctionYes
PROTECTION
OverloadLine Mode105% - 120% for 30 seconds
121% - 150% for 10 seconds
Battery Mode101% - 109% for 10 seconds
110% - 120% for 3 seconds
Surge ProtectionIEC 61000-4-5 Level 3
BypassInternal Bypass (Automatic and Manual)
Short Circuit ProtectionUPS Output Cut Off Immediately
BATTERY
ModelPSB-1000PSB-1500PSB-2000PSB-3000PSB-6000PSB-10K
Type12V 7Ah12V 7Ah12V 7Ah12V 7Ah12V 7Ah12V 9Ah
Quantity34682020
Sealed, Maintenance FreeYES
Typical Recharge Time4 Hr to 90%
External Battery ModuleOption
External Battery ConnectorOption
MANAGEMENT
IndicatorLCD Control Panel
Communication PortRS232, USB (B-type)
SNMP SlotOption
Audible AlarmsYES
PHYSICAL
Power ModuleDimensions (WxDxH) (In)6 x 16.6 x 9.36 x 19.7 x 9.57.9 x 16.6 x 14.110.2 x 23.3 x 22.510.2 x 27.2 x 23.1
Weights (Lbs)33.5436466.4190213
Shipping Dimensions (WxDxH) (In)11.1 x 21.5 x 1411.1 x 24.7 x 1413.4 x 20.7 x 19.116.4 x 30 x 31.516.1 x 34 x 31.5
Weights (Lbs)38.4477072.5206247

* While 208V output, capacity will derated to 90%
* Specifications are subject to change without further notice
* Specifications are for reference, actual information should be based on real product

All UPSs, standard or custom, come with a full 2-year warranty on parts and labor. Well Bilt Power will, at its discretion, repair or replace any product found to be defective. Phone support is included during the 2-year warranty period.